EasyManua.ls Logo

Siemens 6EP4135-0GB00-0AY0

Siemens 6EP4135-0GB00-0AY0
232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Engineering and remote access
3.7 Web server
SITOP UPS1600 / UPS1100
154 Manual, 04.2017, A5E37775406-8-76
Basic device configuration
"Buffering" parameters
Parameter
Value range
Initial value
Connection threshold
21 - 25 V
22.5 V
Buffer time
1 - 32767 s
600 s
Maximum buffer time
1)
Yes / No
No
Additional buffer time after PC shutdown.
3)
1 - 300 s
60 s
Expected buffer current
1)
0 - 40 A
0 A
Reset time:
5 s
Enable reset after buffering
Yes / No
No
1)
Parameter only available from SW version V2.0 and higher
2)
Parameter only available from SW version V2.1 and higher
3)
Valid from V2.0.4 or V2.1

Table of Contents

Related product manuals