Engineering and remote access
3.8 OPC UA server
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76
171
Display name
Data type
Definition
Description
AlarmBatteryTest Boolean PropertyType Battery 'state of health' (SOH) tests are in progress. Output
of SITOP UPS1600 is connected to the battery to detect the
actual capacity of the battery.
AlarmBufferMode
NotPossible
Boolean PropertyType Buffer mode not possible -
check settings, cabling, fuse, and
battery voltages
AlarmBuffer
TimerReset
Boolean PropertyType PC is shutting down
AlarmBuffering
Boolean
PropertyType
Device is in buffer mode
AlarmCommunication
ToDeviceFailed
Boolean PropertyType PROFINET connection available - SITOP UPS1600 is de-
fective
AlarmDevice
Failure
Boolean PropertyType Device failure
AlarmDevice
Overtemperature
Boolean PropertyType Output and battery charging is switched off to prevent dam-
age to the device.
AlarmDevice
ParameterCorrupt
Boolean PropertyType SITOP UPS1600 parameters corrupt - try to update the
software
AlarmDevice
PoweredUp
Boolean PropertyType Device powered up
AlarmDevice
TemperatureHigh
Boolean PropertyType Device temperature is very high! Provide cooling or turn off
unnecessary consumers.
AlarmDevice
TemperatureLow
Boolean PropertyType Device temperature is very low. Care for higher ambient
temperature.
AlarmDevice
TurnedOff
Boolean PropertyType SITOP UPS1600 off - buffer time exceeded or PC was shut
down
AlarmFirmware
UpdateOK
Boolean PropertyType Previous software update was successful - SITOP UPS1600
is operational again.
AlarmFuseBroken
Boolean
PropertyType
Fuse is defective.
AlarmInpu
tVoltageHigh
Boolean PropertyType Input voltage exceeds 30 V. SITOP UPS1600 is not opera-
tional.
Alarm
InsufficientCharge
Boolean PropertyType Set buffer time can currently not be achieved due to low
battery charge.
AlarmLow
VoltageMode
Boolean PropertyType Input voltage of SITOP UPS1600 is too low.
SITOP UPS1600 Buffer is not ready for buffering.
AlarmOutputTurnedOff Boolean PropertyType Output of SITOP UPS1600 has been switched off due to the
execution of a command or because an error situation has
occurred (e.g. temperature or output current too high).
AlarmOutputTurnedOn Boolean PropertyType Output of SITOP UPS1600 has been switched on again due
to the execution of a command or because an error situation
has been remedied.
AlarmOverCurrent Boolean PropertyType Output current of SITOP UPS1600 is too high. Output will
be switched off for 20s. The output will be switched on again
after 20 s.
AlarmResetExecuted Boolean PropertyType Input voltage to SITOP UPS1600 was OK again before the
buffer time expired. Connected devices are reset by switch-
ing off the SITOP UPS1600 outputs for the configured time.
AlarmSurplusBattery Boolean PropertyType More than 6 batteries are connected. Connect only up to 6
batteries at the Energy Storage Link.