Engineering and remote access
3.8 OPC UA server
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76
177
ActualChargingState
Display name
Data type
Definition
Description
ChargeCurrent
Float
AnalogItemType
Actual charging current used to charge battery.
ChargeEndVoltage Float AnalogItemType Battery voltage when charging changes to trickle charging.
Battery is charged 100 %.
ChargeTotalCurrent Float AnalogItemType Battery-specific data: Total charge to the battery during its
service life
ActualState
Display name
Data type
Definition
Description
ModuleCalculated
Capacity
Float AnalogItemType Available battery capacity
ModuleCalculated
Health
Byte AnalogItemType State of health (SoS) as percentage of the rated capacity
ModuleCapacity
Float
AnalogItemType
Capacity
ModuleChange
Recommended
Boolean PropertyType Battery capacity is insufficient to achieve the specified buffer
time.
ModuleCompound Enumeration MultiState
DiscreteType
Connected device
ModuleConnection
Fault
Boolean PropertyType Connection to battery interrupted - check connection and
fuse
ModuleManufactoring
Date
Date PropertyType Manufacturing date of the battery modules.
ModuleMax
Temperature
Sbyte AnalogItemType Maximum specified operating temperature of the battery.
ModuleMin
Temperature
Sbyte AnalogItemType Minimum specified operating temperature of the battery.
ModuleStandbyTime UInt32 AnalogItemType Battery-specific data: Time for which battery was connected
but no power was consumed.
ModuleStateLed Object Sitop_1600_
LedType
ModuleStateLed
ModuleTemperature
Sbyte
AnalogItemType
Battery temperature
ModuleTotalCulled
Current
Float AnalogItemType Battery-specific data: Time for which battery was connected
and power was consumed.
Alarm
Display name
Data type
Definition
Description
AlarmBatteryChange
Canceled
Boolean PropertyType Battery replacement canceled - battery parameters are not
reset
AlarmBatteryChange
FInished
Boolean PropertyType Battery replacement finished - counters have been reset
AlarmBatteryChange
Started
Boolean PropertyType Battery replacement started by user
AlarmBattery
CommunicationFault
Boolean PropertyType Communication with formerly known battery is no longer
possible - check communication