Engineering and remote access
3.3 SIMATIC STEP 7 in the TIA Portal
SITOP UPS1600 / UPS1100
62 Manual, 04.2017, A5E37775406-8-76
●
Total capacity of the installed batteries.
●
Maximum voltage up to which the battery may be charged.
●
The battery is not charged with more than the selected charge current. The
manufacturer's details for the permitted battery charge current must be observed.
Further, the following, device-dependent values apply:
– SITOP UPS1600 10 A: Maximum permissible charge current 3,000 mA
Derating for T
u
> 40 °C or U
in
< 24 V: 2,000 mA
– SITOP UPS1600 20 A: Maximum permissible charge current 4,000 mA
Derating for T
u
> 40 °C or U
in
< 24 V: 3,000 mA
– SITOP UPS1600 40 A: Maximum permissible charge current 5,000 mA
Derating for T
u
> 40 °C or U
in
< 24 V: 3,000 mA
If the battery voltage undershoots this value, it is considered as being faulty by the
SITOP UPS1600 and is not charged.
Activate web server on this module Yes / No Yes (up to V2.0)
Permit access only with HTTPS Yes / No Yes
Log off automatically after 15 minutes
Update interval 0 / 5 s / 10 s / 20 s / 30 s / 60 s 30 s
Set here whether access to the UPS via web server is permitted.
●
Activate web server on this module
Define whether this device can be accessed via the web server.
●
Permit access only with HTTPS
Define whether access is only permissible via HTTPS.
●
Log off automatically after 15 minutes
You define whether a user should be automatically logged off after closing the web
server.
●
You define in which intervals the actual values are sent to the web server.
●
When you enable "Automatic update" then the actual values of the SITOP UPS1600 and
connected supplementary modules are sent to the web server.