Commissioning
8.4 Commissioning using the AOP30 operator panel
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
283
8.4.1.2
Full drive commissioning
Adjust the rated device currents
Note
The US rating must be set at p50067 for Base Drives (type 6RA80xx
-
2xxxx) manufactured in
North America.
The
rated armature DC current for the device
must be adjusted by setting p50076[0] (in %)
or p50067 if:
Maximum armature current < 0.5 × rated armature DC current for the device
The
rated field DC current for the device
must be adapted by setting p50076[1] (in %) if:
Maximum field current < 0.5 × rated field DC current for the device
Adapt to the actual device supply voltage
p50078[0]
Rated input voltage for converter armature (in volts)
p50078[1]
Rated input voltage for converter field (in volts)
Acquiring the motor data
The motor data can be taken from the motor rating plate.
Figure 8-4 Example of a rating plate