Commissioning
8.5 Commissioning with the STARTER commissioning tool
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
313
⇒ Select the
● [0] No field
● [1] Field also switched with the main contactor
● [2] Standstill field at >= o7.0 (factory setting)
● [3] Field is continuously switched on
● [4] Field also switched with signal auxiliaries ON
● [21] External field device, otherwise the same as position 1
● [22] External field device, otherwise the same as position 2
● [23] External field device, otherwise the same as position 3
● [24] External field device, otherwise the same as position 4
⇒ Select whether the EMF-dependent field weakening should be activated or deactivated.
is activated, then a valid field characteristic must be available (p50117 =
1), otherwise, the optimization run for field weakening (p50051 = 27) must be carried out.
⇒ Depending on the selection under
, the values for
,
and
can be set.
⇒ Click
>