Commissioning
8.5 Commissioning with the STARTER commissioning tool
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
313
Select the
field control:
[0] No field
[1] Field also switched with the main contactor
[2] Standstill field at >= o7.0 (factory setting)
[3] Field is continuously switched on
[4] Field also switched with signal auxiliaries ON
[21] External field device, otherwise the same as position 1
[22] External field device, otherwise the same as position 2
[23] External field device, otherwise the same as position 3
[24] External field device, otherwise the same as position 4
Select whether the EMF-dependent field weakening should be activated or deactivated.
Note
If Field weakening
is activated, then a valid field characteristic must be available (p50117 =
1), otherwise, the optimization run for field weakening (p50051 = 27) must be carried out.
Depending on the selection under
Field control
, the values for
field supply voltage
,
standstill field (%)
and
delay time
can be set.