431
Encoder lines of incremental encoder
For encoders with sin/cos 1Vpp:
Encoder lines = No. of sinusoidal signal periods
Error code in Gn_XIST2
Table 10- 19 Error code in Gn_XIST2
n_XIST2
Meaning
Possible causes / description
1 Encoder fault One or more existing encoder faults.
Detailed information in accordance with drive messages.
2
Zero mark monitoring
3 Abort parking sensor
Parking drive object already selected.
4 Abort find reference mark
A fault exists (Gn_ZSW.15 = 1)
Encoder has no zero mark (reference mark)
Reference mark 2, 3 or 4 is requested
Switchover to "Flying measurement" during search for reference mark
Command "Read value x" set during search for reference mark
Inconsistent position measured value with distance-coded reference marks.
5 Abort retrieve reference
value
More than four values requested
No value requested
Requested value not available
6 Abort flying measurement
No probe configured p0488, p0489
Switch over to "reference mark search" during flying measurement
Command "Read value x" set during flying measurement
7 Abort get measured value
More than one value requested
No value requested
Requested value not available
Parking encoder active
Parking drive object active
8 Abort absolute value
transmission on
Absolute encoder not available
Alarm bit absolute value protocol set
3841
Function not supported
Encoder 2 status word (G2_ZSW)
See Gn_ZSW