Figure 5-12 Starting and monitoring the forced dormant error detection (test stop)
Parameter Description
p9559 Forced dormant error detection timer (Factory setting: 8 h)
Monitoring time for the forced dormant error detection of the extended functions.
p9659 Forced dormant error detection timer (Factory setting: 8 h)
Monitoring time for the forced dormant error detection of the basic functions.
r9660 Forced dormant error detection remaining time
Displays the remaining time up to performing the forced dormant error detection of the
basic functions.
p9705 Forced dormant error detection signal source (Factory setting: 0)
Signal source for the forced dormant error detection of the basic functions and the
extended functions.
r9723.0 1 signal: Forced dormant error detection of the extended functions is necessary
Signal for the higher-level control.
r9765 Forced dormant error detection remaining time
Displays the remaining time up to performing the forced dormant error detection of the
extended functions.
r9773.31 1 signal: Forced dormant error detection of the basic functions is required
Commissioning
5.12 Setting extended functions
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
150 Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD