Figure A-8 Diagram 2 - acceptance test SLS with stop reaction STOP B
Procedure
To perform the acceptance test of the SLS function, proceed as follows:
Status
If you are using multiple SLS levels, repeat the test for each of the SLS levels.
1. The inverter is ready
Check the following:
The inverter signals neither faults nor alarms of the safety functions (r0945[0…7],
r2122[0…7]).
SLS is not active (r9722.4 = 0).
Go online with the STARTER and configure the following trace:
Trigger on variable - bit pattern (r9722.7 = 0)
Record the following values: r9714[0], r9714[1], r9722
Display the bits r9722.0/.4/.7/.9/.10
Select the interval and pretrigger so you can recognize when the active SLS limit has
been exceeded and the subsequent drive responses.

Appendix
A.2 Examples of acceptance tests
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD 395

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals