SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the operating mode for flying restart.
The flying restart allows the drive converter to be powered up while the motor is still rotating. In so doing, the drive
converter output frequency is changed until the actual motor speed/velocity is found. The motor then accelerates up
to the setpoint at the ramp-function generator setting.
Value: 0: Flying restart inactive
1: Flying restart always active (start in setpoint direction)
4: Flying restart always active (start only in setpoint direction)
Dependency: A differentiation is made between flying restart for U/f control and for vector control (p1300).
Flying restart, U/f control: p1202, p1203, r1204
Flying restart, vector control: p1202, p1203, r1205
For synchronous motors, flying restart cannot be activated.
Refer to: p1201
Refer to: F07330, F07331
Notice: The "flying restart" function must be used in cases where the motor may still be running (e.g. after a brief line supply
interruption) or is being driven by the load. The system might otherwise shut down as a result of overcurrent.
Note: When p1200 = 1, 4: Flying restart is active after faults, OFF1, OFF2, OFF3.
When p1200 = 1: The search is made in both directions.
When p1200 = 4: The search is only made in the setpoint direction.
For U/f control (p1300 < 20), the following applies:
The speed can only be sensed for values above approx. 5 % of the rated motor speed. For lower speeds, it is
assumed that the motor is at a standstill.
If p1200 is changed during commissioning (p0010 > 0), then it is possible that the old value will no longer be able to
be set. The reason for this is that the dynamic limits of p1200 have been changed by a parameter that was set when
the drive was commissioned (e.g. p0300).
Description: Sets the signal source to enable the "flying restart" function.
Dependency: Refer to: p1200
Note: Withdrawing the enable signal has the same effect as setting p1200 = 0.
p1200[0...n] FlyRest oper mode / FlyRest op_mode
Access level: 2 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0 4 0
p1201[0...n] BI: Flying restart enable signal source / Fly_res enab S_src
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 1

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals