List of Parameters
Parameters
1-303
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the configuration for the motorized potentiometer of the technology controller.
Dependency: Refer to: r2231, p2240
Notice: For p0014 = 1, the following applies:
After the value has been modified, no further parameter modifications can be made and the status is shown in
r3996. Modifications can be made again when r3996 = 0.
Note: Re bit 00:
0: The setpoint for the motorized potentiometer is not saved and after ON is entered using p2240.
1: The setpoint for the motorized potentiometer is saved and after ON is entered using r2231. In order to save in a
non-volatile fashion, bit 03 should be set to 1.
Re bit 02:
0: Without initial rounding-off
1: With initial rounding-off.
The selected ramp-up/down time is correspondingly exceeded. The initial rounding-off is a sensitive way of specify-
ing small changes (progressive reaction when keys are pressed). The jerk for initial rounding is independent of the
ramp-up time and only depends on the selected maximum value (p2237).
It is calculated as follows:
r = 0.0001 x max(p2237, |p2238| ) [%] / 0.13^2 [s^2]
The jerk is effective until the maximum acceleration is reached (a_max = p2237 [%] / p2247 [s] or a_max = p2238
[%] / p2248 [s]), after which the drive continues to run linearly with constant acceleration. The higher the maximum
acceleration (the lower that p2247 is), the longer the ramp-up time increases with respect to the set ramp-up time.
Re bit 03:
0: Non-volatile data save de-activated.
1. The setpoint for the motorized potentiometer is saved in a non-volatile fashion (for p2230.0 = 1).
Re bit 04:
When the bit is set, the ramp-function generator is computed independent of the pulse enable. The actual output
value of the motorized potentiometer is always in r2250.
Description: Displays the setpoint memory for the motorized potentiometer of the technology controller.
For p2230.0 = 1, the last setpoint that was saved is entered after ON.
Dependency: Refer to: p2230
p2230[0...n] Technology controller motorized potentiometer configuration / Tec_ctr mop config
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
- - 0000 0100 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Data save active Yes No -
02 Initial rounding-off active Yes No -
03 Non-volatile data save active for p2230.0 =
1
Yes No -
04 Ramp-function generator always active Yes No -
r2231 Technology controller motorized potentiometer setpoint memory / Tec_ctrl mop mem
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Data set: -
Units group: 9_1 Unit selection: p0595
Min Max Factory setting
- [%] - [%] - [%]

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals