Parameters
List of Parameters
1-302
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the signal source to select the fixed value of the technology controller.
Dependency: Refer to: p2220, p2221, p2222
Description: Displays the selected and effective fixed value of the technology controller.
Dependency: Refer to: r2229
Description: Displays the status word for the fixed value selection of the technology controller.
Description: Displays the number of the selected fixed setpoint of the technology controller.
Dependency: Refer to: r2224
p2223[0...n] BI: Technology controller fixed value selection bit 3 / Tec_ctrl sel bit 3
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 0
r2224 CO: Technology controller, fixed value effective / Tec_ctr FixVal eff
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Data set: -
Units group: 9_1 Unit selection: p0595
Min Max Factory setting
- [%] - [%] - [%]
r2225.0 CO/BO: Technology controller fixed value selection status word / Tec_ctr FixVal ZSW
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Technology controller fixed value selected Yes No 7950,
7951
r2229 Technology controller number actual / Tec_ctrl No. act
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -