List of Parameters
Parameters
1-327
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Displays the measured Control Unit temperature.
An appropriate message is output when 87 °C is exceeded.
Index: [0] = Temperature actual
[1] = Temperature maximum
Dependency: Refer to: A01009
Note: The value of -200 indicates that there is no measuring signal.
Re r3960[0]:
Displays the currently measured Control Unit temperature.
Re r3960[1]:
Displays the highest measured Control Unit temperature. This value is saved on the module in a non-volatile fash-
ion.
Description: Displays the status word for the drive unit.
Description: Displays the counter reading for modified BICO interconnections on this device.
The counter is incremented by one for each modified BICO interconnection.
Description: Setting to acknowledge all active faults of a drive object.
Note: Parameter should be set from 0 to 1 to acknowledge.
After acknowledgement, the parameter is automatically reset to 0.
r3960[0...1] Control Unit temperature measured / CU temp measured
CU240E-2
CU240E-2 DP
CU240E-2 DP F
CU240E-2 F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2006 Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- [°C] - [°C] - [°C]
r3974 Drive unit status word / Drv_unit ZSW
Access level: 1 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Software reset active Yes No -
01 Writing of parameters disabled as parame-
ter save in progress
Yes No -
02 Writing of parameters disabled as macro is
running
Yes No -
r3978 BICO CounterDevice / BICO CounterDevice
Access level: 4 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
p3981 Faults, acknowledge drive object / Faults ackn DO
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 1 0

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals