Parameters
List of Parameters
1-390
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the fail-safe digital input (F-DI) for the "SS1" function.
Value: 0: Statically active
1: F-DI 0
2: F-DI 1
3: F-DI 2
255: Statically inact
Dependency: Refer to: p10023
Note: If value = 0:
No terminal assigned, safety function always active.
If value = 255:
No terminal assigned, safety function always inactive.
F-DI: Failsafe Digital Input
SS1: Safe Stop 1
Description: Sets the fail-safe digital input (F-DI) for the "SLS" function.
Value: 0: Statically active
1: F-DI 0
2: F-DI 1
3: F-DI 2
255: Statically inact
Dependency: Refer to: p10026
Note: If value = 0:
No terminal assigned, safety function always active.
If value = 255:
No terminal assigned, safety function always inactive.
F-DI: Failsafe Digital Input
SLS: Safely-Limited Speed
p10123 SI SS1 input terminal (processor 2) / SI SS1 F-DI P2
CU240E-2 DP F
CU240E-2 F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: C(95) Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 255 0
p10126 SI SLS input terminal (processor 2) / SI SLS F-DI P2
CU240E-2 DP F
CU240E-2 F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: C(95) Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 255 0

Table of Contents

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals