Parameters
List of Parameters
1-240
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the configuration for the test pulse evaluation.
Re bit 00:
Check for conductor-to-conductor short circuit when pulse is enabled.
Note: Re bit 00:
If the test was successful once after POWER ON (see r1902.0), it is not repeated.
If a conductor-to-conductor short-circuit is detected during the test, this is displayed in r1902.1.
Description: Displays the status of the test pulse evaluation.
Short-circuit test:
Bit 0: The short-circuit test was run without any faults detected.
Bit 1: A phase short circuit has been detected.
p1901 Test pulse evaluation configuration / Test puls config
Access level: 4 Calculated: - Data type: Unsigned32
Can be changed: T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Phase short-circuit test pulse active Yes No -
r1902 Test pulse evaluation status / Test puls ev stat
Access level: 4 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Short-circuit test executed Yes No -
01 Phase short-circuit detected Yes No -