Functions
5.7 Closed-loop control
CU240S and CU240E Control Units, FW 3.2
Operating Instructions, 03/2009, A5E02440075B AA
113
5.7.2.2 Commissioning vector control
Vector control with and without speed encoder requires careful commissioning and therefore
must only be performed by commissioning engineers that are experienced in handling this
type of control.
Steps when commissioning the vector control
1. Carry out quick commissioning (P0010 = 1)
In order to ensure that the vector control functions perfectly, it is absolutely imperative
that the motor data is entered correctly
2. Run the motor data identification (P1900 = 2)
The motor data identification must be carried out with the motor in the cold state. The
motor data identification must be carried out after the quick commissioning as the quick
commissioning supplies output data for the motor model and the motor data identification
makes these even more precise
3. Carry out the automatic speed controller optimization (P1960 = 1)
Table 5- 34 The most important vector control parameters
Parameter Description
P0003 = 2 Extended access
P1300 = 20 Control type: Vector control without speed encoder
P0300 …
P0360
Motor data are transferred from the motor rating plate during the quick commissioning
and calculated with the motor data identification
P1442 …
P1496
Speed controller parameters
P1511 = … Additional torque
P1520 = … Upper torque limit
P1521 = … Lower torque limit
P1530 = … Motoring power limit
P1531 = … Regenerative power limit
For more information about this function, refer to the parameter list as well as the function
diagrams 7000, 7500, 7700, 7800 and 7900 in the List Manual.
You will find additional information in the Internet
(http://support.automation.siemens.com/WW/view/en/7494205
):
0