Commissioning
4.7 Data backup with the operator panel and memory card
CU240S and CU240E Control Units, FW 3.2
Operating Instructions, 03/2009, A5E02440075B AA
77
4.7 Data backup with the operator panel and memory card
4.7.1 Saving and transferring data using the BOP
The operator panel as a medium to backup and transfer data
You can save a parameter set on the operator panel and transfer it to other inverters, e.g. to
identically parameterize several devices or to transfer the settings after a device has been
replaced.
Prerequisites for transferring data sets from the operator panel to a different inverter
The Control Unit to which the parameter set is transferred must be of the same type and
have the same firmware release as the source Control Unit. (Same 'type' means: The same
Order No.)
Saving the parameters on the operator panel (upload)
Table 4- 13 Transfer data from the inverter to the operator panel
Parameters Description
P0003 = 3 3: Expert
P0010 = 30 30: Initiating parameter transfer
P0802 = 1 1: Transfer data from theEEPROM (of the inverter) to the operator panel
If the upload procedure is successful, P0010 and P0802 are set to 0 and the "RDY"
LED lights up.
If the download procedure is unsuccessful, F0055 or F0057 is displayed and the
LED "SF" (red) lights up. In this case, make another attempt to transfer data.
Transferring parameters from the operator panel into the inverter (download)
Table 4- 14 Transfer data from the operator panel to the inverter
Parameters Description
P0003 = 3 3: Access level 3
P0010 = 30 30: Initiating parameter transfer
P0803 = 1 1: Transfer data to theEEPROM (of the inverter) from the operator panel
If the upload procedure is successful, P0010 and P0803 are set to 0 and the "RDY"
LED lights up.
If the download procedure is unsuccessful, F0055 or F0057 is displayed and the
LED "SF" (red) lights up. In this case, make another attempt to transfer data.