EasyManua.ls Logo

Siemens CU240S PN-F - Three-Wire Control, Method 2

Siemens CU240S PN-F
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
5.2 Inverter control
CU240S and CU240E Control Units, FW 3.2
Operating Instructions, 03/2009, A5E02440075B AA
91
5.2.6 Three-wire control, method 2
Function description
The first control command is a permanent enable signal for starting the motor. When this
enable signal is canceled, the motor stops.
The motor is started with the positive edge of the second control command.
The third control command defines the direction of rotation.
R
R
R
&RPPDQGLJQRUHG
$FWLYH
$FWLYH
$FWLYH
$FWLYH
$FWLYH
(QDEOH
VLJQDO
0RWRU21
5HYHUVH
PRWRU
0RWRU
VSHHG
W
2))
Figure 5-6 Three-wire control using digital inputs, method 2
Table 5- 11 Function table
Enable
signal
Motor
ON
Reverse
motor
Function when motor is at a
standstill
Function when motor is
rotating
0 Not
relevant
Not relevant No effect OFF1: The motor decelerates
to a standstill
1 0→1 0 The motor accelerates to the
setpoint
No effect
1 0→1 1 The motor accelerates to the
inverted setpoint
No effect
1 0 1→0 No effect The motor reverses to the
setpoint.
1 0 0→1 No effect The motor reverses to the
inverted setpoint.

Table of Contents