EasyManua.ls Logo

Siemens CU240S PN-F - Page 92

Siemens CU240S PN-F
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
5.2 Inverter control
CU240S and CU240E Control Units, FW 3.2
92 Operating Instructions, 03/2009, A5E02440075B AA
Table 5- 12 Parameterizing the function
Parameter Description
P0700 = 3 Controls the motor using the digital inputs of the inverter
P0727 = 3 Three-wire control, method 2
P0701 = 2 The enable signal to power-up the motor is issued with digital input 0
Further options:
The enable signal can be issued with any other digital input, e.g. with digital input 3
via P0704 = 2
P0702 = 1 The motor is started with digital input 1
Further options:
The motor can be started with any other digital input, e.g. with digital input 3 via
P0704 = 1
P0703 = 12 The direction of the motor is reversed with digital input 2
Further options:
The direction of the motor can be reversed with any other digital input, e.g. with
digital input 3 via P0704 = 12