EasyManua.ls Logo

Siemens CU240S PN-F - Dimensions, Hole Drilling Templates, Minimum Clearances, Tightening Torques

Siemens CU240S PN-F
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connection
3.3 Mounting Power Modules
CU240S and CU240E Control Units, FW 3.2
Operating Instructions, 03/2009, A5E02440075B AA
31
3.3.1 Dimensions, hole drilling templates, minimum clearances, tightening torques
Overview of dimensions and hole drilling templates for the Power Modules
0.37 kW … 1.5 kW 2,2 kW … 4 kW 7,5 kW … 15 kW
Retaining type
2 x M4 bolts
2 x M4 nuts
2 x M4 washers
Retaining type
4 x M4 bolts
4 x M4 nuts
4 x M4 washers
Retaining type
4 x M5 bolts
4 x M5 nuts
4 x M5 washers
Tightening torques
2.5 Nm (22.1 lbf.in)
Tightening torques
2.5 Nm (22.1 lbf.in)
Tightening torques
2.5 Nm (22.1 lbf.in)
Distances from other devices
Lateral: 0 mm (0 inch) up to 40°C
30 mm (1.18 inch) from 40°C and
higher
Top/bottom: 100 mm (3.93 inch)
Clearances to other devices
Lateral: 0 mm (0 inch) up to 40°C
40 mm (1.57 inch) from 40°C and
higher
Top/bottom: 100 mm (3.93 inch)
Clearances to other devices
Lateral: 0 mm (0 inch) up to 40°C
50 mm (1.96 inch) from 40°C and
higher
Top/bottom: 125 mm (4.92 inch)
Depth
Standalone: 145 mm (5.71 inch)
With CU240E: 187 mm (7.36 inch)
With CU240S: 208 mm (8.19 inch)
Depth
Standalone: 165 mm (6.50 inch)
With CU240E: 207 mm (8.15 inch)
With CU240S: 228 mm (8.98 inch)
Depth
Standalone: 185 mm (7.28 inch)
With CU240E: 227 mm (8.94 inch)
With CU240S: 248 mm (9.76 inch)