Functions
5.10 Technological functions
CU240S and CU240E Control Units, FW 3.2
144 Operating Instructions, 03/2009, A5E02440075B AA
Automatic restart characteristics
Table 5- 62 Overview of the automatic restart characteristics
ON command always active (continuously) ON command in the de-energized
state
Fault F0003 due to All other faults
P1210
Power
failure
Line supply
undervoltage
Before
power failure
in
operation
Inverter
signals a fault
Before power
failure
Inverter ready
Before power
failure
0 --* --* --* --* --* --*
1 Fault
acknowledgeme
nt
--* Fault
acknowledgeme
nt
--* Fault
acknowledgement
--*
2 Fault
acknowledgeme
nt + restart
--* --* --* --* Restart
3 Fault
acknowledgeme
nt + restart
Fault
acknowledgement
+ restart
Fault
acknowledgeme
nt + restart
Fault
acknowledgeme
nt + restart
Fault
acknowledgement
+ restart
--*
4 Fault
acknowledgeme
nt + restart
Fault
acknowledgement
+ restart
--* --* --* --*
5 Fault
acknowledgeme
nt + restart
--* Fault
acknowledgeme
nt + restart
--* Fault
acknowledgement
+ restart
Restart
6 Fault
acknowledgeme
nt + restart
Fault
acknowledgement
+ restart
Fault
acknowledgeme
nt + restart
Fault
acknowledgeme
nt + restart
Fault
acknowledgement
+ restart
Restart
*) -- = no action

Table of Contents