EasyManua.ls Logo

Siemens CU240S PN-F - Page 165

Siemens CU240S PN-F
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
5.11 Operation in fieldbus systems
CU240S and CU240E Control Units, FW 3.2
Operating Instructions, 03/2009, A5E02440075B AA
165
Set the DIP switch to address 10 (as shown in the following table).
Table 5- 75 Examples of setting the PROFIBUS address
DIP switch 1 2 3 4 5 6 7
Address = values added in this line 1 2 4 8 16 32 64
Example 1:
Address = 117 = 1 + 4 + 16 + 32 + 64
OFF
ON
Example 2:
Address = 39 = 1 + 2 + 4 + 32
OFF
ON
The valid address range is specified in the table below:
Table 5- 76 Valid PROFIBUS addresses
DIP switch settings Significance
0 PROFIBUS address defined via P0918
1 … 125 Valid PROFIBUS address
126, 127 Invalid PROFIBUS address
Integrating the inverter into a higher-level SIMATIC control
Once you have set the PROFIBUS address of the inverter, all the remaining settings
required for integrating it in the SIMATIC control are carried out in STEP 7 with HW Config.
Creating a STEP 7 project
Create a new STEP 7 project and assign a project name (e.g. "G120_in_S7").
Figure 5-23 Create a new project in STEP 7
352),%86
352),%86

Table of Contents

Related product manuals