Functions
5.11 Operation in fieldbus systems
CU240S and CU240E Control Units, FW 3.2
174 Operating Instructions, 03/2009, A5E02440075B AA
Integrating the inverter into a higher-level SIMATIC control
All settings required for integrating the inverter in the SIMATIC controller are carried out in
STEP 7 with HW Config.
Creating the STEP 7 project and configuring SIMATIC 300
The procedure here is very similar to that described for PROFIBUS. The main differences
are:
1. In the module catalog, choose a PROFINET-capable S7 controller (e.g. CPU 315-2
PN/DP).
2. Once you have added the SIMATIC 300, create a PROFINET network.
Figure 5-31 Add SIMATIC 300 station with the PROFINET network
352),1(7
352),1(7