Parameter data record
A.2 Parameter validation errors
Technology Module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)
168 Manual, 05/2019, A5E35061186-AB
Error codes
The following table shows the module-specific error codes and their meaning for parameter
data record 128.
Table A- 7 Error codes for parameter validation
Error code in STATUS parame-
ter (hexadecimal)
Meaning
Solution
Byte 0
Byte 1
Byte 2
Byte 3
DF
80
B0
00
Data record number unknown
Enter valid number for data record.
DF
80
B1
01
Length of data record incorrect
Enter valid value for data record length.
DF 80 B2 00 Slot invalid or not available
Check whether module is inserted or removed.
Check assigned values for parameters of the
WRREC instruction.
DF 80 E0 01 Wrong version
Check byte 0.
Enter valid values.
DF 80 E0 02 Error in the header information
Check byte 1.
Correct the length of parameter blocks.
DF 80 E1 00 Parameter invalid: No detailed information
available
Check all parameter values.
DF
80
E1
11
"Operating mode" parameter invalid
Enter valid parameter value.
DF
80
E1
12
"Reaction to CPU STOP" parameter invalid
Enter valid parameter value.
DF 80 E1 18 "Set function of DI" parameter configured the
same for DI0 and DI1.
Enter different parameter values for DI0 and DI1.
DF 80 E1 19
"Edge selection" parameter invalid
"Gate start (edge-triggered)" configured as
function for DIm and "At rising and falling
edge"
"Gate stop (edge-triggered)" configured as
function for DIm and "At rising and falling
edge"
"Synchronization" configured as function for
DIm and "At rising and falling edge"
Enter valid parameter value.
Configure "Gate start (edge-triggered)" as function
for DIm only together with "At rising edge" or "At
falling edge"
Configure "Gate stop (edge-triggered)" as function
for DIm only together with "At rising edge" or "At
falling edge"
Configure "Synchronization" as function for DIm
only together with "At rising edge" or "At falling
edge"
DF
80
E1
1A
"Input delay" parameter invalid
Enter valid parameter value.
DF 80 E1 1B Value above the high limit of the parameter
"Period duration"
Enter a parameter value of maximum 85000000
D
.
DF
80
E1
1C
Value above high limit of parameter "On delay"
Enter a parameter value of maximum 85000000
D
.
DF 80 E1 1D Value above high limit of parameter "Minimum
pulse duration"
Enter a parameter value of maximum 85000000
D
.
DF
80
E1
1E
Value above high limit of parameter "Off delay"
Enter a parameter value of maximum 85000000
D
.
DF 80 E1 20 Value above high limit of parameter "Reference
value current"
Two-channel operation: Enter parameter value of
maximum 2000
D
.
One-channel operation: Enter a parameter value of
maximum 4000
D
.