Parameter data record
A.2 Parameter validation errors
Technology Module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)
Manual, 05/2019, A5E35061186-AB
169
Error code in STATUS parame-
ter (hexadecimal)
Meaning
Solution
Byte 0
Byte 1
Byte 2
Byte 3
DF 80 E1 21 Value below low limit of the parameter "Period
duration"
Without High-speed output: Enter a parameter value
of at least 100
D
.
With high-speed output: Enter a parameter value of at
least 10
D
.
DF 80 E1 22 "Dithering" activated, although "Pulse width
modulation PWM" mode is not configured
Disable "Dithering"
DF 80 E1 23 "High-speed output (0.1 A)" enabled in the
"PWM with DC motor" mode or in one-channel
operation
Disable "High-speed output (0.1 A)"
DF 80 E1 24 "Current control" activated, even though "Pulse
width modulation PWM" mode is not configured
Deactivate "Current control"
DF 80 E1 25 "High-speed output (0.1 A)" and "Current con-
trol" enabled in "Pulse width modulation PWM"
mode
Disable "High-speed output (0.1 A)" or "Current con-
trol"
DF 80 E1 26 "HW enable" for DIn.0 configured in "On/Off
delay" mode
In the "On/Off delay" mode, do not configure "HW
enable"
DF 80 E1 27 Manipulated value low limit >= Manipulated
value high limit
Manipulated value low limit < Manipulated value high
limit
DF 80 E1 28
Dithering period duration < 4 × PWM period
duration
Dithering period duration < 2 ms
Dithering period duration >= 4 × PWM period
duration
Dithering period duration > 2 ms
DF 80 E1 29 "1" is configured for both substitute values
(DQn.A and DQn.B).
Only configure "1" for DQn.A or DQn.B.
DF
80
E1
F0
Reserved bit is not set to 0.
Set reserved bit to 0.