Parameter data record
A.2 Parameter validation errors
Technology Module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)
Manual, 05/2019, A5E35061186-AB
169
Error code in STATUS parame-
ter (hexadecimal)
DF 80 E1 21 Value below low limit of the parameter "Period
duration"
Without High-speed output: Enter a parameter value
of at least 100
D
.
With high-speed output: Enter a parameter value of at
D
DF 80 E1 22 "Dithering" activated, although "Pulse width
modulation PWM" mode is not configured
Disable "Dithering"
DF 80 E1 23 "High-speed output (0.1 A)" enabled in the
"PWM with DC motor" mode or in one-channel
Disable "High-speed output (0.1 A)"
DF 80 E1 24 "Current control" activated, even though "Pulse
width modulation PWM" mode is not configured
Deactivate "Current control"
DF 80 E1 25 "High-speed output (0.1 A)" and "Current con-
trol" enabled in "Pulse width modulation PWM"
mode
Disable "High-speed output (0.1 A)" or "Current con-
trol"
DF 80 E1 26 "HW enable" for DIn.0 configured in "On/Off
In the "On/Off delay" mode, do not configure "HW
DF 80 E1 27 Manipulated value low limit >= Manipulated
Manipulated value low limit < Manipulated value high
DF 80 E1 28
• Dithering period duration < 4 × PWM period
duration
• Dithering period duration < 2 ms
• Dithering period duration >= 4 × PWM period
duration
• Dithering period duration > 2 ms
DF 80 E1 29 "1" is configured for both substitute values
Only configure "1" for DQn.A or DQn.B.
Reserved bit is not set to 0.