14
Smart Infrastructure A6V10393190_h_en_--
2019-09-01
3.3 Technical data
You will find information on approvals, CE marking, and the relevant EU directives for
this device (these devices) in the following document(s); see 'Applicable documents'
chapter:
· Document A6V10371354
FC121-ZA FC122-ZA FC123-ZA FC124-ZA
Zones
Number of zones 2 4 8 12
Number of detectors per zone Up to 32 Up to 32
Inputs
Number of inputs 2 3
Outputs
Number of monitored outputs
- Mainboard 2 2
- Output cards (Optional) 2
4 6
Number of relay outputs
- Mainboard 1 1
- Output cards (Optional) 2
4
6
Number of optional output cards 1
2
3
Alarm counter
9999 alarms 9999 alarms
History log
1000 events 1000 events
3.3.1 Electrical data
FC121-ZA FC122-ZA FC123-ZA FC124-ZA
Zone
Operating voltage
- Standard zone
- GB continuity zone
DC 16.5…19 V
DC 21…28.6 V
DC 16.5…19 V
DC 21…28.6 V
Line resistance / capacitance
Collective & Conventional
device
- GB continuity
- Mixed zone
Used Conventional device
- Standard
- Short=alarm
Collective & Conventional
device
- Standard
- Short=alarm zone
≤50 Ω / ≤1 μF
1,2,4,6
≤50 Ω / ≤1 μF
1,2,4,6
≤100 Ω / ≤1 μF
1,2,4,5
≤100 Ω / ≤1 μF
1,4
≤80 Ω / ≤1 μF
1,2,3,4,5,6
≤80 Ω / ≤1 μF
1,3,4
≤50 Ω / ≤1 μF
1,2,4,6
≤50 Ω / ≤1 μF
1,2,4,6
≤100 Ω / ≤1 μF
1,2,4,5
≤100 Ω / ≤1 μF
1,4
≤80 Ω / ≤1 μF
1,2,3,4,5,6
≤80 Ω / ≤1 μF
1,3,4
Detector 110-series;
Detector FDOOT241-X, OOH740, FDF221-9, FDF241-9, FDL241-9;
3
Detectors series DS11, Synova Series 600C;
4
Synova Series 300C;
5
Conventional MCP;
6
Collective MCP
Alarm trigger Z-Diode 5.6 V or resistor 410…820 Ω Z-Diode 5.6 V or resistor 410…820 Ω