4.4 Outputs
Outputs are used to transmit system status information. As a result three different types
are available: Monitored, Supervised and Relay.
4.4.1 Mainboard (OUT1 / OUT2)
Functionality 'Monitored line':
The panel monitors the line in terms of open and short circuits from the panel to the
EOL element.
Application:
Sounder controls, fire outputs and dialer
Technical:
- Max. current
FC121-ZA and FC122-ZA à 24 V / 0.5 A
FC123-ZA and FC124-ZA à 24 V / 1 A
- Each line must be terminated with EOL element (Diode 1N4007)
- Supervised functionality: Not available
Programming:
- Configure g Output g Output 1 – n g Mode g Sounder control
4.4.2 Output card (OUTA / OUTB)
The output can be either programmed as 'Monitored' or 'Supervised'.
Functionality 'Monitored line':
The panel monitors the line in terms of open and short circuits from the panel to the
EOL element.
Application:
Sounder controls, fire outputs and dialer
Technical:
- Max. current 24 V / 1 A
- Each line must be terminated with EOL element (Diode 1N4007)
Programming:
- Configure g Output g Output 4 – n g Mode g Sounder control
COM NO
OUT1
OUT3
–
+
OUT2
+
–
NONC
NONC
–
+
–
+
–
+
Mainboard
Monitored
Relay
Output card
Monitored or
Supervised
Relay