EasyManua.ls Logo

Siemens FC122-ZA - 7 Programming; Configure; Zone

Siemens FC122-ZA
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
55
Smart Infrastructure A6V10393190_h_en_--
2019-09-01
7 Programming
For programming, access level 3 is required.
All outputs are automatically isolated during programming mode.
All disabled outputs are automatically enabled if access level 2 is reached.
7.1 Configure
7.1.1 Zone
Configure parameter for each zone.
Select a zone for programming.
Standard
Automatic detectors
and manual call
points can be mixed
within the same
zone.
Device could be
either conventional
or collective.
AVC option
'1', '2'
Mixed MCP & det.
AVC option
'1', '2', '3'
GB continuity
If detectors are removed, the
zone will work properly.
Short = alarm
Any short is detected as 'Fire
Alarm'.
Direct
'1'
No delay, immediate alarm.
Via V1 / V2
'2' Delayed alarm. V1: reaction time, 3 min.
V2: investigation time, 5 min.
(Change value, see
chapter 7.2.10).
Via AVC timer
MCP direct
'3'
- Delayed alarm for automatic
detectors.
- No delay for MCPs.
If selected, the 'Alarm' state is achieved, if the second device activation in the same zone
occurs within 90 seconds. The first device activation is inhibited from the zone and
automatically reset after a defined time, (default value: 15 second, see chapter 7.2.5).
If selected, the 'Alarm' state is achieved, if the second corresponding zone is in 'Alarm' as well.
The zone pairs (1&2, 3&4, 5&6, etc) are predefined in the system,
e.g. if zone 6 is selected, zone 5 is automatically linked as well and vice versa.
Name the zone, see chapter 7.5.
*Do NOT use this function in combination with FDOOT241-9 (ES<13). For detailed
information refer to document A6V10393192.
Customer
text
Zone
coincidence
*Device
coincidence
AVC
Mode
Zone 1..n
Zone
Accessory
card(s)
InputOutputZone
Configure

Table of Contents

Other manuals for Siemens FC122-ZA

Related product manuals