5.4 Buttons
The following buttons are available:
No. Description Function
1 MORE ALARM Move to the next 'fire alarm'.
2 RESET Reset the fire control panel to quiescent condition.
3 ACKNOWLEDGE
· Starts the investigation time V2 (AVC).
· Silence the buzzer until a new alarm event occurs.
· Silence the sounder until a new event occurs (if programmed).
4 SILENCE BUZZER Silence the buzzer until a new event (alarm, alert or fault) occurs.
5 SILENCE
· Silence the sounder control(s) in the event of alarm.
RESOUND
· Manually re-activate the sounder control(s) during alarming.
· If programmed, activation of all sounder control(s)
(activation mode only in quiescent condition).
6
MANNED /
UNMANNED
· Switch between manned / unmanned.
· Cancel the alarm delay V1 / V2 when V1 / V2 is running.
7 LAMP TEST Activate all LEDs, the buzzer and the display on the PMI.
8 CANCEL Move one step back without saving the change.
9 OK Confirm the selected value.
10 MENU Enter the main menu.
11 NAVIGATION
· Select the menu or change the time: <p> and <q>.
· Change the selection: <t> and <u>.
· Change to the next level or select value in the checkbox: <u>.
1 432
6
7
5
9
10
8
11