EasyManua.ls Logo

Siemens FC122-ZA - Mechanical Data

Siemens FC122-ZA
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15
Smart Infrastructure A6V10393190_h_en_--
2019-09-01
FC121-ZA FC122-ZA FC123-ZA FC124-ZA
EOL element
- Standard zone
- Short=alarm
- Mixed zone
- GB continuity zone
18V TVS
18V TVS
18V TVS
10 μF capacitor
18V TVS
18V TVS
18V TVS
10 μF capacitor
Monitored output mainboard
Voltage / Current (max.) 24 V / 0.5 A 24 V / 1.0 A
EOL element Diode (1N4007) Diode (1N4007)
Relay output mainboard 1.0 A @ DC 30 V
1.0 A @ DC 30 V
AUX. power output (max.) DC 24 V / 200 mA
DC 24 V / 500 mA
Power supply
Mains voltage AC 196…253 V AC 196…253 V
or
AC 97…127 V
Mains fuse F1 AC 250 V @ 1.6 AT
AC 250 V @ 2.5 AT
AC 115 V @ 2.5 AT
Power consumption 25 W 70 W
Max. nominal output current with
battery charging, I
max a
max. 0.3 A max. 0.9 A
Max. nominal output current
without battery charging, I
max b
max. 0.9 A max. 2.5 A
Min. output current I
min
0.1 A 0.1 A
System supply voltage DC 21…28.6 V DC 21…28.6 V
Mains failure delay 0…30 min. / default 5 min. 0…30 min. / default 5 min.
Battery low discharge cut off DC 20.5 V…DC 21 V DC 20.5 V…DC 21 V
Temperature compensation Yes Yes
Battery
Operation time Up to 72 h Up to 72 h
Battery size 2 x 12 V, 4.5 Ah / 7 Ah, lead acid
2 x 12 V, 7 Ah / 12 Ah / 17 Ah, lead
acid
Voltage DC 21…28.6 V DC 21…28.6 V
Load resistance R
imax
max. 2.5 Ω max. 1.0 Ω
3.3.2 Mechanical data
FC121-ZA FC122-ZA FC123-ZA FC124-ZA
Terminals 0.2...2.5 mm
2
Dimensions (W x H x D) 360 x 310 x 85 mm 430 x 399 x 124 mm
Weight 2.0 kg without batteries 4.5 kg without batteries
Color
- Housing, Cover
grey, ~RAL-Design 000 50 00

Table of Contents

Other manuals for Siemens FC122-ZA

Related product manuals