Smart Infrastructure A6V10393190_h_en_--
2019-09-01
4.3 Zone modes
4.3.1 Standard
The Standard line supports collective and conventional devices within the same zone.
Technical:
- Each line must be terminated with EOL element Transzorb diode (18 V TVS).
- Max. 32 devices on each line
Programming:
- Configure g Zone g Zone 1 – n g Mode g Standard
Zone mode 'Standard' complies with EN 54-2 and EN 54-13.
ZONE1
ZONE n
–
+
–
+
–
+
5
6
5
6
5
6