Smart Infrastructure A6V10393190_h_en_--
2019-09-01
6.1.3 Procedure with Alarm Verification
In the event of a fire alarm, the reaction timer V1 gets started.
Press the <ACKNOWLEDGE> button to confirm
the attendance. If the alarm event is
acknowledged, the buzzer turns off.
è Access level 2 password is required.
The investigation timer V2 is started.
Optional:
Silence the sounder by pressing <RESOUND /
SILENCE> button.
Action is requested
During the investigation time, examine the location of the fire and decide whether it is
a MAJOR INCIDENT or MINOR INCIDENT.
MAJOR INCIDENT: A real fire emergency
Cancel the investigation time by pressing the
<MANNED / UNMANNED> button.
è Access level 2 password is required.
MINOR INCIDENT: No fire alarm
Reset the system to normal operation by pressing
<RESET> button.
è Access level 2 password is required.
Notice
The fire alarm reoccurs if any device remains in fire condition.
Normal Operation
Siemens FC12X
22.12.2012 08:08
Fire alarm 2:00
Zone 1 1/1
Meeting room 1
Fire alarm 3:00
Zone 1 1/1
Meeting room 1
Fire alarm 2:00
Zone 1 1/1
Meeting room 1