81
Smart Infrastructure A6V10393190_h_en_--
2019-09-01
Fault description
LED
Status
Cause / Action
Sounder fault 3 Fast
Any fault on sounder lines is indicated.
See display for detailed information and
check common issues:
- Short / break
- Missing EOL element
- If output is supervised à calibrate line
Alarm dialer fault 4 Fast
Fault of alarm dialer line
See display for detailed information and
check common issues:
- Short / break
- Missing EOL element
- If output is supervised à calibrate line
12.2 System
Fault description Cause / Action
Set date & time fault. Power down, requires date & time, chapter 6.4.6.
Buzzer does not work. Check the setting, chapter 7.2.12.
12.3 Accessories
Fault description Cause / Action
DC 24 V is too low. Check voltage input '24V In' on the output card(s) 2M2R.
All four outputs from one
output card 2M2R indicate
a fault.
Locate the faulty output card according to chapter 4.6.2.
- Ribbon cable connected properly, chapter 4.6.2.
- Output card programmed, chapter 7.1.4.
The EVAC module
indicates a fault.
Check the following:
- Ribbon cable connected properly, chapter 4.6.3.
- EVAC module enabled, chapter 7.1.4.
Key switch set No indication is given, change the device.
LED indication field No indication is given, change the device.
lease contact your service provider
if you cannot eliminate troubles.