EasyManua.ls Logo

Siemens FC122-ZA - 5 Function Overview; Operating Functions; Access Levels

Siemens FC122-ZA
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
37
Smart Infrastructure A6V10393190_h_en_--
2019-09-01
5 Function overview
5.1 Operating functions
The operating functions are related to the following topics.
Alarm Disable / Enable System test
- Acknowledge
- Reset
- Silence sounder
- Manned / unmanned
- Cancel alarm delay
- Zone
- Sounder control
- Fire output
- Alarm dialer
- Fault dialer
- Mode walk test with
sounder activation for
1 second
- LED test
5.2 Access levels
The FC12x provides four different access levels.
Access
level
Password Function
1 No need End user to view pending events.
2 5555
or
key switch
Instructed and authorized end user:
- Switch on / off zones and outputs.
- Automatic logout after 2 minutes of no operation.
- Password is not necessary if a key switch is used.
3 6666 Commissioning personnel:
- System programming.
- Automatic logout after 10 minutes of no operation.
- The basic function of panel will not continue.
4 6666
and front
cover open
Commissioning personnel:
- Save and restore site configuration.
- Upload history log.
- Update firmware.
6669 - Reset alarm counter.

Table of Contents