FC122-ZA 4 zone panel 54 123
Out 1 (e.g. Sounders)
Out 2 (e.g. Sounders)
Aux. output
Accessory cards
FCA1203-Z1
(1st)
Output card 2M 2R 12 25
Out A&B (e.g. Sounders)
FTO1203-H1 EVAC Module 0.5 2.2
Standby current [A]
Alarm current [A]
If the total current of the outputs (Sounders, etc.) is higher than
power supply is required.
In order to reduce the total current:
- Power the output A&B from the external power supply (possible per card).
Move the Auxiliary output to the external power supply.
Choose the appropriate battery size depending on the calculated capacity.
[(Standby time × Standby current) + (Alarm time × sum alarm current)] × Aging factor = Capacity (max.12 Ah)
_ _ h × 0._ _ _ A + 0.5 h × _._ _ _ A × 1.25 =
Standby time [h]: 24, 30 or 72
Alarm time [h]: 0.5 hour
Aging factor: 1.25
Standby current [A]: Total current in standby mode
Alarm current [A]: Total current in alarm mode
Capacity [Ah]: 4.5 Ah; 7 Ah