Siemens Building Technologies Basic Documentation LMV51... CC1P7550en
HVAC Products 7 Display and operating unit AZL5... 01.10.2003
After pressing ENTER, the following display appears:
O2 | Load : 23 . 5
4.5|Fuel :23.2
Man | A i r : 41 6
:23.5|Aux :33.3
This menu enables the installer to manually change the output by using incrementing or
decrementing commands, letting the actuators operate on interpolated straight lines
(outside the parameterized curvepoints: Extrapolation). Above that, the currently
acquired O2 value will now be shown if a PLL52.110A200 O2 module and an O2 sensor
are connected to the system.
Traveling to the output preset here can be stopped by pressing ESC.
The actual curve settings are made by adjusting the entire ratio control system based on
the roughly predefined curvepoints and outside the already defined points. After
pressing ENTER again, new points can be introduced at the required positions.
Then, the values can be changed:
Po i n t |
Load : 28 . 5
:3|Fuel:28.4
O2 | Ai r : 45 . 2
4.5|Aux :31.3
The further setting procedure is the same as that used with «Edit individual point».
Example: Adjustment of the ratio control system via manual control
Prerequisite: No curvepoints are parameterized.
1. Activating program stop
On menu: «Params & Display» → «Ratio Control» → «Program Stop»
→ parameterize from «deactivated» to «Stop_Ph24»
2. Starting the system
On menu: «Params &. Display» → «Ratio Control» → «Settings Gas / Oil» → «Special
Positions» → «Autom / Manual / Off»
or on: «Manual Operation» Æ «Autom / Manual / Off» to «Burner on»
and confirm.
3. Setting the prepurge positions
The system commences the startup sequence and stops in phase «Driving to Prepurge
24». Now, the prepurge positions can be set on menu «SpecialPositions». Then, on
«ProgramStop», change to «Stop_Ph36.
4. Setting the ignition positions
The system continues the startup sequence and stops in phase «Driving to ignition
position 36». Now, the ignition positions can be set on menu «SpecialPositions».
Then, on «ProgramStop», set to «Stop_Ph72», if operation shall immediately follow.
To readjust the ignition positions after the burner has ignited: «ProgramStop» to
«Stop_Ph44», or «Stop_Ph52» for pilot ignition after the pilot flame has been shut
down. Then, on «ProgramStop», set to «Stop_Ph72».

Table of Contents

Other manuals for Siemens LMV5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMV5 Series and is the answer not in the manual?

Siemens LMV5 Series Specifications

General IconGeneral
BrandSiemens
ModelLMV5 Series
CategoryControl Systems
LanguageEnglish

Related product manuals