Siemens Building Technologies Basic Documentation LMV51... CC1P7550en
HVAC Products 7 Display and operating unit AZL5... 01.10.2003
Setting multistage ratio control
With multistage ratio control, the position values can be changed in 2 different ways:
1. Presetting the positions with no response by the actuators in order to fine-adjust the
points later using «Followed».
2. Setting the switching and operating positions from «below» using «Followed». This
means that stage 1 must be adjusted first, followed by the next switching on point,
etc.
Ac tua t or
Pos i t i ons
fol lowed
not fol lowed
When the switch on / off and operating positions have been parameterized with «Not
followed», the values can be changed. The system maintains its current load stage.
The menu offers the choice of «Followed» or «Not followed». The display is maintained
while the settings are made.
When accessing the menu, the operating positions «Stage 1» appear.
By pressing the SELECTION buttons the entered positions of all switching and
operating points can be viewed. This has no impact on the system, even if «Followed»
has been selected.
Example: Not followed.
Punk t I Lu f t : 28 . 5
:BS1 IHilf1:28.4
O2 I :
4.3I :

Table of Contents

Other manuals for Siemens LMV5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMV5 Series and is the answer not in the manual?

Siemens LMV5 Series Specifications

General IconGeneral
BrandSiemens
ModelLMV5 Series
CategoryControl Systems
LanguageEnglish

Related product manuals