Parameterdarstellung auf Basis der Menüstruktur AZL - Ebene «OEM» - Auslieferstand Siemens Landis&Staefa
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6 Description Value range Access
rights
Default
parameter
setting
LMV51 LMV52
122/278
Siemens Building Technologies Basic Documentation LMV51... CC1P7550en
HVAC Products 7 Display and operating unit AZL5... 01.10.2003
Volume Oil R Fuel volume oil (resettable) 0..199999999,9 l
0..199999999,9 gal
User 0 x x
Reset Date Gas Reset date fuel volume gas 01.01.00..31.12.99
01-01-00..12-31-99
User 0 x x
Reset Date Oil Reset date fuel volume oil 01.01.00..31.12.99
01-01-00..12-31-99
User 0 x x
LockoutCounter Total number of lockouts that occurred (read only) 0..65535 User 0 x x
CombEfficiency 0..200% User - x
BurnerID Identification of burner 4..15 characters User invalid x x
OptgModeSelec
t
Operating mode selection of AZL for serial port and eBus User x x
InterfacePC Setting the serial port (RS-232) of the AZL to interface
operation for PC tool
User x x
GatewayBASon Activating the eBus port on the AZL for BAS User x x
GatewayBASoff Deactivating the eBus port on the AZL User x x
ManualOperation Menu level for activating manual operation with the
preselected load
User x x
SetLoad Set target load 0..100%, S1, S2, S3 User - x x
Autom/Manual/O
ff
Selection of manual or automatic operation Automatic
Burner on
Burner off
User Automatic x x
Params & Display Menu level for making the parameter settings User x x
BurnerControl Setting the burner control parameters User x x
Times Service x x
TimesStartup1 Burner control startup times 1 Service x x
MinTmeStartRel Minimum time for start release 0.2..63 s OEM 1s x x
FanRunupTme Fan runup time 0.2..63 s OEM 2s x x
PrepurgeTmeGa
s
Prepurge time gas MinT_PrepurgeGas..63
min
Service 20s x x
PrepurgeTmeOil Prepurge time oil MinT_PrepurgeOil..63 min Service 15s x x
MinT_PrepurgeG
as
Minimum prepurge time gas 0.2..63 min OEM 20s x x

Table of Contents

Other manuals for Siemens LMV5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMV5 Series and is the answer not in the manual?

Siemens LMV5 Series Specifications

General IconGeneral
BrandSiemens
ModelLMV5 Series
CategoryControl Systems
LanguageEnglish

Related product manuals