Parameterdarstellung auf Basis der Menüstruktur AZL - Ebene «OEM» - Auslieferstand Siemens Landis&Staefa
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6 Description Value range Access
rights
Default
parameter
setting
LMV51 LMV52
129/278
Siemens Building Technologies Basic Documentation LMV51... CC1P7550en
HVAC Products 7 Display and operating unit AZL5... 01.10.2003
AuxActuator 1 Auxiliary actuator 1 for firing on gas: Deactivate / activate / air-
regulating
deactivated
activated
air influen
OEM deactivated x
AuxActuator 2 Auxiliary actuator 2 for firing on gas: Deactivate / activate / air-
regulating
deactivated
activated
air influen
OEM deactivated x
AuxActuator 3 Auxiliary actuator 3 for firing on gas: Deactivate / activate / air-
regulating
deactivated
activated
air influen
OEM deactivated x
VSD VSD for firing on gas: Deactivate / activate / air-regulating deactivated
activated
air influen
OEM deactivated x
OilSettings Parameter settings for firing on oil Service x x
SpecialPosition
s
Setting the special actuator positions for firing on oil Service x x
HomePos Setting the home positions for firing on oil Service x x
HomePosOil Home position of fuel damper (oil) 0..90° Service 0° x x
HomePosAir Home position of air damper (oil) 0..90° Service 0° x x
HomePosAux Home position of auxiliary damper (oil) 0..90°
0..100%
Service 0° x x
HomePosAux2 Home position of auxiliary damper 2 0..90° Service 0° x
HomePosAux3 Home position of auxiliary damper 3 0..90° Service 0° x
HomePosVSD Home position of VSD 0..100% Service 0° x
PrepurgePos Setting the prepurge positions for firing on oil Service x x
PrepurgePosAir Prepurge position of air damper (oil) 0..90° Service 90° x x
PrepurgePosAux Prepurge position of auxiliary damper (oil) 0..90°
0..100%
Service 90° x x
PrepurgePosAux
2
Prepurge position of auxiliary damper 2 0..90° Service 90° x
PrepurgePosAux
3
Prepurge position of auxiliary damper 3 0..90° Service 90° x

Table of Contents

Other manuals for Siemens LMV5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMV5 Series and is the answer not in the manual?

Siemens LMV5 Series Specifications

General IconGeneral
BrandSiemens
ModelLMV5 Series
CategoryControl Systems
LanguageEnglish

Related product manuals