Parameterdarstellung auf Basis der Menüstruktur AZL - Ebene «OEM» - Auslieferstand Siemens Landis&Staefa
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6 Description Value range Access
rights
Default
parameter
setting
LMV51 LMV52
141/278
Siemens Building Technologies Basic Documentation LMV51... CC1P7550en
HVAC Products 7 Display and operating unit AZL5... 01.10.2003
SerialNumber Serial number 0..65535 User - x x
ParamSet Code Preselected parameter set: customer code 0..255 User 20 x x
ParamSet Vers Preselected parameter set: version 0..65535 User 400 x x
5 AuxActuator2 User x
ASN Type reference 1..15 characters User "SQM45.29" x
ProductionDate Date of production 01.01.00..31.12.99
01-01-00..12-31-99
User - x
SerialNumber Serial number 0..65535 User - x
ParamSet Code Preselected parameter set: customer code 0..255 User 20 x
ParamSet Vers Preselected parameter set: version 0..65535 User 400 x
6 AuxActuator3 User x
ASN Type reference 1..15 characters User "SQM45.29" x
ProductionDate Date of production 01.01.00..31.12.99
01-01-00..12-31-99
User - x
SerialNumber Serial number 0..65535 User - x
ParamSet Code Preselected parameter set: customer code 0..255 User 20 x
ParamSet Vers Preselected parameter set: version 0..65535 User 400 x
SW Version User x x
1 AirActuator SW version of actuator 0..65535 User - x x
2 GasActuat(Oil) SW version of actuator 0..65535 User - x x
3 OilActuator SW version of actuator 0..65535 User - x x
4 AuxActuator SW version of actuator 0..65535 User - x x
5 AuxActuator2 SW version of actuator 0..65535 User - x
6 AuxActuator3 SW version of actuator 0..65535 User - x
VSD Module Settings for the VSD module User x x
Configuration Service x x
Speed Service x x
Num Puls per R Number of pulses per revolution 3..6 Service 3 x x
Standardization Standardization process for fan speed deactivated
activated
Service - x x
StandardizedSp Standardized speed: Speed corresponding to 100 % 1..6300 Service 1 x x