Parameterdarstellung auf Basis der Menüstruktur AZL - Ebene «OEM» - Auslieferstand Siemens Landis&Staefa
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6 Description Value range Access
rights
Default
parameter
setting
LMV51 LMV52
142/278
Siemens Building Technologies Basic Documentation LMV51... CC1P7550en
HVAC Products 7 Display and operating unit AZL5... 01.10.2003
Setpoint Output Configuration of analog interface 0..20 mA
4..20 mA
Service 4..20 mA x x
Setteling Time Time between speed readjustment and speed acquisition for
long run commands
(8..200) * 25 ms OEM 16 x x
Fuel Meter Service x x
PulseValueGas Number of pulses per volume unit gas 0,0000..9999,9999
Imp/m³
0,00000..999,99999
Imp/ft³
Service 1 x x
PulseValueOil Number of pulses per volume unit oil 0,0000..9999,9999 Imp/l
0,0000..9999,9999
Imp/gal
Service 1 x x
Process Data User x x
Max Stat Dev Maximum speed deviation at the end of a run command 0..100% User - x x
Max Dyn Dev Maximum speed deviation when accelerating 0..100% User - x x
Num Dev >0.3% Number of speed deviations >0.3 % at the end of a run
command
0..255 User - x x
Num Dev >0.5% Number of speed deviations >0.5 % at the end of a run
command
0..255 User - x x
Absolute Speed Absolute speed 0..6553,5 User - x x
ProductID User x x
ASN Type reference 1..15 characters User - x x
ProductionDate Date of production 01.01.00..31.12.99
01-01-00..12-31-99
User - x x
SerialNumber Serial number 0..65535 User - x x
ParamSet Code Preselected parameter set: customer code 0..255 User 20 x x
ParamSet Vers Preselected parameter set: version 0..65535 User 400 x x
SW Version SW version of VSD 0..65535 User - x x
O2 Module Settings for the O2 module User x
Configuration Service x