LMV Series
Technical Instructions
LV5-1000
Menu Path Parameter Default Range Description
51.1
52.2
52.4
LEGEND - Password Access: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function
LMV
Params & Display>
O2 Module
SW Version (U) Software version of the O2 module (PLL module).
x x
FGR-Mode (S)
Aux3on
Curve
Aux3onCurve
time
temperature
temp.contr.
TCautoDeact
deactMinpos
auto deact
Sets the mode of the FGR hold for the Aux 3 actuator. Seven seperate operating modes exist.
These are:
1) Aux3onCurve- Function deactivated and Aux 3 actuator always operates on its
programmed curve.
2) time - Aux 3 actuator stays at ignition position until DelayTimeFGR Gas(Oil) timer expires.
3) temperature - Aux 3 actuator stays at ignition position until ThresholdFGR Gas(Oil)
temperature is reached.
4) temp.contr. - Position of Aux 3 actuator is based on flue temp, Factor FGR Gas(Oil) , and
the programmed curve for the Aux 3 actuator (LMV52.4 only).
5) TCautoDeact - same as Temp.contr but automatically deactivates if there is a fault with the
flue gas sensor (LMV52.4 only).
6) deactMinpos - after ignition position, Aux 3 actuator is held closed (LMV52.4 only).
7) auto deact - do not select this option. It is displayed if the FGR hold was deactivated due
to a sensor issue (LMV52.4 only).
/ x
FGR-sensor (S)
X86PtNi
1000
X86PtNi1000
X60 Pt1000
X60 Ni1000
Selects the type and wiring location of the flue gas sensor for the FGR functions.
x x
actTmpFGR-sensor (U) The actual temperature read by the selected FGR sensor can be viewed at this parameter.
x x
T
hresholdFGR Gas(Oil) (S) 752 F 32-1562 F
This sets the temperature that must be achieved to release the Aux 3 actuator to modulate.
Only has an effect if parameter FGR-Mode is set to "temperature".
x x
DelaytimeFGR Gas(Oil) (S) 300s 0-63min
This sets the time that must elapse before the Aux 3 actuator is released to modulate. Only
has an effect if parameter FGR-Mode is set to "time".
x x
Factor FGR Gas(Oil) (S) 100% 10-100%
Adjustment of calculated temperature dependent position of the Aux 3 actuator. An
adjustment of less than 100% reduces the position of the Aux 3 actuator. 100% means no
adjustment. Factor only has an effect when FGR temperature is different than when ratio
curves were commissioned.
x
Read Only
Read Only
Params & Display>
Flue Gas Recirc.
SCC Inc. Page 42 Section 3
HOME
HOME
P - LIST

Table of Contents

Other manuals for Siemens LMV51.140C1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMV51.140C1 and is the answer not in the manual?

Siemens LMV51.140C1 Specifications

General IconGeneral
BrandSiemens
ModelLMV51.140C1
CategoryControl Systems
LanguageEnglish

Related product manuals