EasyManua.ls Logo

Siemens LMV51.140C1 - Using the O Alarm Functionality Without O Trim

Siemens LMV51.140C1
374 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LMVSeriesTechnicalInstructions
DocumentNo.LV51000
SCCInc. Page25 Section6
4. InitContrO
2
controlispreparingtoengagebutisstilllocked
5. LockTLoadO
2
controlisengagedbutlocked(inprecontrol)duetoaloadchange
6. ActiveO
2
controlisactivelytrimmingbasedonsetpointandmeasuredO
2
value
7. LockTCAct‐O
2
controlisengagedbutlockedduetoanexcursionfromsetpoint
IfthestateoftheO
2
controlisshownas"locked",parameterDiagRegStatewillshowthereasonwhy.
DiagRegState
Menupath:Params&Display>O2Contr/Alarm>ProcessData
ThisparametershowsthereasonthattheO
2
controlislocked.Possiblevaluesare:
0TheloadisbelowtheloadlimitsetbyparameterO2CtrlThreshold
1Theloadcontrollerisinautotune
2TheO
2
sensorisbeingtestedforresponse(selfcheckofO
2
sensor)
3ThefuelairratioorO
2
trimcurvesarebeingprogrammed
4Themeasured%O
2
isabovetheleanlimitorbelowtherichlimit
5ThereisanerrorinthePLL52module
6Thereisanerrorintheprecontrol
UsingtheO
2
AlarmFunctionalitywithoutO
2
Trim
Aswaspreviouslymentioned,theO
2
systemcanberunindifferentmodes.Themodesaresetusing
parameterOptgMode,whichcanbefoundusingthefollowingmenupath:
Menupath:Params&Display>O2Contr/Alarm>Gas/OilSettings
Theavailableoperatingmodesare:
1. Mandeact‐deactivatesallO
2
trimandO
2
alarmfunctionality.%O
2
valuecanstillbeviewed.
2. O2Limiter‐OnlytheO
2
alarmisactive.Thismeansthatalockoutwilloccuriftheleanlimit(O2
MaxValue)isexceededforatimelongerthanwhatissetforparameterTimeO2Alarm.Likewise,a
lockoutwilloccuriftherichlimit(O
2
alarmcurve)isexceededforatimelongerthanwhatissetfor
parameterTimeO2Alarm.Notrimfunctionalityisactive.
3. O2Control‐ThesameasO2Limiter,exceptO
2
trimisnowenabled.Exceedingrichorleanlimits
willcausealockoutinthesamewayastheO2Limitermode.
4. ConAutoDeacInthismode,exceedingtherichorleanlimitswillnotcauseanimmediatelockout.
ExceedingtherichorleanlimitswillcausetheO
2
trimtobetemporarilydeactivated.Afterawaiting
timeof3timesTau,themeasured%O
2
willbereevaluated.Ifthe%O
2
ishigherthantherichalarm,
theO
2
trimwillbedeactivated.Ifthe%O
2
islowerthantherichalarm,alockoutwilloccur.TheO
2
trimcanbeautomaticallydeactivatedandreactivatedthenumberoftimesallowedbyparameter
NumMinUntilDeact.Themaximumse ttingis5.Ifmorethan5deactivationsandreactivations
occur,thentheO
2
trimmodewillbechangedto“autodeact”untiltheO
2
trimcontrolismanually
reactivated.
5. Autodeact‐indicatesthattheO
2
trimhasbeenautomaticallydeactivatedforsomereason.See
errorcodesinSection7.Donotselectthismode.
HOME

Table of Contents

Other manuals for Siemens LMV51.140C1

Related product manuals