EasyManua.ls Logo

Siemens LMV51.140C1 - AZL Says Measurement Not Successful When Measuring the Delay Time for O 2 Trim

Siemens LMV51.140C1
374 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LMVSeriesTechnicalInstructions
DocumentNo.LV51000
SCCInc. Page17 Section7
AZLSaysMeasurementnotSuccessfulWhenMeasuringtheDelayTimeforO2Trim
WhensettingthelowfirepointorthehighfirepointontheO
2
controlcurve,theAZLmeasures
whatiscalledthe“delaytime”(Tautime).Thedelaytimeisdefinedasthelengthoftimeit
takesachangeintheairdamperpositiontobedetectedbytheO
2
sensor.Thistimeislongerat
lowfireandshorterathighfireduetogasvelocity.Ifanerroroccurswhiletryingtomeasure
thisdelaytime,theAZLsaysMeasurementnotSuccessful”.
Totroubleshootthis,checkthefollowing:
1) VerifythatOptgModeissetto“mandeact”usingthefollowingmenupath:
Params&Display>O2Contr/Alarm>Gas/OilSettings>OptgMode
2) VerifythatLowfireAdaptPtNoissetto2(combustioncurvepoint2)orhigherifdesired.By
default,thisparameterissetto“X”(undefined).
Themenupathforthisparameteris:
Params&Display>O2Contr/Alarm>Gas/OilSettings>ControlParam>
LowfireAdaptPtNo
3) Ifbothoftheaboveparametersaresetcorrectly,thenitispossiblethattheO
2
readingson
theratiocontrolcurveweresetincorrectly.WhensettingeachpointontheO
2
control
curve,theLMV5willpromptwiththemessage“WhenvaluestablecontinuewENTER”.
PressingENTERthensetsthe%O
2
fortheratiocontrolcurve.IfENTERispressedtooearly
beforetheO
2
valuehasstabilized,anonrepresentativeO
2
valuewillbeenteredforthe
ratiocontrolcurve.Ifthisisthecase,gobackintotheO
2
controlcurveandateachpoint
waittogetastablereadingbeforepressingENTERtoensurethattheO
2
readingis
representativeofthecurrentairdamperposition.3060secondsisnottoolongtowait
oncethearrow(>)turnsintoacolon(:)indicatingthattheactuatorshavestoppedmoving.
HOME

Table of Contents

Other manuals for Siemens LMV51.140C1

Related product manuals