TechnicalInstructions  LMVSeries
DocumentNo.LV51000
Section6 Page2 SCCInc.
Introduction
TheLMV52.240andtheLMV52.440bothhaveO
2
(oxygen)trimandO
2
alarm(previouslycalled
“monitor”)capability.Inaddition,theLMV52.440offersadvancedfeaturessuchastemperature
compensatedlightoffandmoredynamicO
2
trimcapabilities.Ingeneral,theLMV52.440is
recommendedformoredifficultapplica tionssuchaslowandultralowNOxburnerswheretheburner
stabilitybandismuchsmallerthanatraditionalnozzle mixingburner.Somefeatures intheLMV52.440
werespecificallydesignedforultralowNOxmeshburners.
TheO
2
trimfunctionsbyusinganinsituO
2
sensorinstalledintheboilerstack,andthenadjusting
actuatorsand/orVSDtomaintaina%O
2
setpoint.Onlyairrelated(airinfluenced)actuatorsare
adjusted,thustheO
2
trimdoesnotadjustthefiringrate(fuelrelatedload).Onlytheairrate(airrelated
load)isadjusted.
EachRatioControlCurvePointthatisentered(seeSection4)willhaveacorrespondingO
2
trimsetpoint,
richlimit(O
2
alarm)andleanlimit(O
2
maxvalue).TheexceptiontothisruleisthatO
2
trimcannotbe
performedonPoint1.If10pointsareenteredontheRatioControlCurve,therewillbe9trimpoints
and10richlimit(O
2
alarm)points.Having10pointsontheRatioControlCurveisrecommended.
AsisthecasewithadvancedsystemssuchasO
2
trim,thefundamentalsystemsthatlieunderneaththe
advancedsystemmustbeinplaceandworkingcorrectlytoenabletheadvancedsystemtowork
correctly.Forexample,ifthegaspressuresupplyisnotrepeatableupstreamofthefiringratecontrol
valve(fundamentalsystem),thentheO
2
trim(advancedsystem)islikelytodeactivate.The
fundamentalsystemsontheburner/boilerthatmustbeworkingcorrectlyareoutlinedindetailinthe
PreRequisiteslistedinSection4.ThePreRequisitesforLMV52systemswithO
2
trimmustbemet
beforeO
2
trimcommissioningisattempted.
IfthePreRequisitesaresatisfied,thenreliableoperationoftheO
2
trimdependsoncorrectparameter
settingsfortheapplicationandcorrectcommissioningoftheO
2
trim.Thissectionwilloutlinethebasics
behindhowtheO
2
trimsystemoperates,andwilloutlinethetypicalcommissioningprocedurefora
traditionalnozzlemixingburner(standardemissions)andapremixmeshburner(loworultralowNOx).
NozzlemixingburnersthatuseahighpercentageofFGRtoachievelowNOxtypicallybehaveinaway
thatissimilartoapremixmeshburner,sothecommissioningprocedureforthese
typesofburnersis
similartoapremixmeshburner.
O
2
Trim(O
2
Control)Fundamentals
Bydefinition,anO
2
trim(O
2
control)systemmonitorsthelevelofO
2
intheexhaustgasesoftheboiler
andadjuststhefuelorairflowtomaintainanO
2
setpoint.TheLMV52accomplishesthistaskbyreading
the%O
2
(wetbasis)withaninsituO
2
sensorandbyadjustingtheangularpositionofairflowinfluenci ng
actuators.IftheburnerisequippedwithaVSD(variablespeeddrive)fortheblower,theO
2
trimcan
alsoadjusttheblowerspeedtoinfluencetheburn erairflow.
HOME

Table of Contents

Other manuals for Siemens LMV51.140C1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMV51.140C1 and is the answer not in the manual?

Siemens LMV51.140C1 Specifications

General IconGeneral
BrandSiemens
ModelLMV51.140C1
CategoryControl Systems
LanguageEnglish

Related product manuals