Properly adjustedPIDvalues will result inthepressure / temperature staying within+/‐3% of
setpointwithoutconstantlychangingtheloadandmodulatingtheactuators.
PPart (Proportional Band)‐Increases firing rate based on how far below setpoint the
temperature / pressure is.Smaller values cause a more aggressive P response to a drop in
pressure / temperature relative to setpoint.Values that are too small will cause hunting.
Typicalsetting:10% to30%.
IPart (Integral)‐Serves to eliminate steady state "droop" caused by the proportional band
setting.Thus, this works hand in hand with PPart to bring the pressure / temperature up to
setpoint.Smallervaluescause amore aggressiveIresponse(asetting of1ismostaggressive).
Valuesthataretoosmallwillcauseovershoot.Typicalsetting:80secto300sec.Asettingof0
deactivatesthefeature,butthisisnotrecommended.
DPart (Derivative)‐Serv
es to eliminate overshoot, and allows a more aggressive integral
setting.Larger values cause a more aggressive D response.DPart is not needed on many
steam boilers.If neede d, small values of less than 20 typically work well.A setting of 0
deactivatesthefeature.Largevalueswilltypicallycausehunting.
8. AfterthePIDloophasbeenadjusted,itispossiblethattheloadwillstillmoveupand downbya
small amount (12% load).If this is the case, adjusting parameter MinActuatorStep may help
eliminatethis"microhunting".Thisparametercanbefoundinthefollowingmenu:
Params&Display>LoadController>ControllerParam
MinActuatorStepisbasicallyadeadbandfortheoutputofthePIDloop.Typicalsetting:
1%to
4%.Valuesabove5%couldcausehuntingissuesinsomeapplications.
SuggestedColdStart(ThermalShockProtection)Setup
The LMV51.1 and LMV52 have an internal load control and therefore have the ability to perform
thermalshockprotection.ThermalshockprotectiononlyfunctionswhentheLMV5isinaninternalload
controllermode,namelyIntLC,IntLCX62,orIntLCBus(seechartonpreviouspages).
Thecold startfeaturerequiresthatthetemperatureorpressureofthe boileris measuredby asensor
connectedtotheLMV5.
Forahot waterboiler(temperatur
ebasedmodulation),the sametemperaturesensor thatisusedfor
modulationmustbeusedforthecoldstartfeature.Forasteamboiler(pressurebasedmodulation),a
temperature sensor is also highly recommended for cold start.Temperat
ure senso rs are highly
recommended since pressure does not always represent temperature in a nonfiring steam boiler,
especiallywhenmultiplesteamboilersarepipedtothesamesteamheader.Theparagraphsbelow will
onlymentiontemperaturebasedcol dstart,butthesameideasalsoapplytopressurebasedcoldstart.
HOME

Table of Contents

Other manuals for Siemens LMV51.140C1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMV51.140C1 and is the answer not in the manual?

Siemens LMV51.140C1 Specifications

General IconGeneral
BrandSiemens
ModelLMV51.140C1
CategoryControl Systems
LanguageEnglish

Related product manuals