1. Thecommissi oningprocedureassumesthefollowing:
a. AllPreRequisitesforanLMV52systemwithO
2
trim(andVSDifequipped)havebeenmet
accordingtoSection4ofthisliterature.
b. TheRatioControlCurveshavebeencommissionedaccordingtoSection4ofthisliterature.
c. Section6ofthisliteraturehasbeenreadand un derstooduptothispoint.
2. AswasthecasefortheRatioControlCurvesinSection4,thesamefreespreadsheetcanalsobe
usedtoassistinthecommissioningoftheO
2
trim.ThisspreadsheetgraphicallyillustratestheO
2
curvesaswellasprovidesanorderlywaytorecordthedetailsofhowtheburnerwassetup.
Figure63:LMVxCurvesSpreadsheet
3. ThekeytocommissioningtheO
2
curvesquicklyandeasilyiscontainedintheRatioControlCurves.
Specifically,thefollowingmustbeachievedforeachpointontheRatioControl Curves(as
paraphrasedfromSection4ofthisliterature):
a. Safe,efficientcombustionasverifiedbyacalibratedstackgasanalyzer
b. The%loadmatchingthefuelflowwithin+/‐3%
c. Emissionscompliance
d. SmoothRatioControlCurves(nosharppeaksorvalleys)
e. VSDspeedshouldincreasewithloadinalinearfashion(ifequipped)
f. Findandreco
rdthe%O
2
wetcorrespondingtothefuelrichlimit(O2Alarmvalue)foreachpoint
byprobing.*
g. Findandrecordthe%O
2
wetcorrespondingtothefuelleanlimit(O2MaxValue)forPoint1and
Point10byprobing.*
h. Lastbutnotleast,leavethecurvepointssothatthe%O
2
wetis2%higherthanthefuelrichlimit
(O2Alarmvalue).Recordthisasthe"saved"valueforeachcurvepoint.
*NOTE:Whenprobingthefuelrichlimit,itisnotrecommendedtoexceed200PPMCO(drybasis)
orlessthan1.0%O
2
(wetordrybasis)foranypoint.Whenprobingthefuelleanlimit,itisnot
recommendedtoexceed200PPMCOoradverselyaffectflamestabilityforanypoint.