LMVSeriesTechnicalInstructions
DocumentNo.LV51000
SCCInc. Page15 Section6
*NOTE:Whenprobingthefuelrichlimit,itisnotrecommendedtoexceed200PPMCO(drybasis)
orlessthan1.0%O
2
(wetordrybasis)foranypoint.Whenprobingthefuelleanlimit,itisnot
recommendedtoexceed200PPMCOoradverselyaffectflamestabilityforanypoint.
NOTE:The%O
2
valuesreadanddisplayedbytheLMV52systemarealwaysonawetbasis(%O
2
wet).Mostifnotallexternalexhaustgasanalyzersreadanddisplay%O
2
andothergasesonadry
basis(%O
2
dry).AllO
2
curvesmustbecommissionedusing%O
2
wetvaluesasreadbytheLMV52.
TheexternalexhaustgasanalyzerisusedtoreadCO,NOx,andalsoservesasawaytodouble
checkthe%O
2
wetvalues.Figure611givestheapproximaterelationshipbetween%O
2
wetand
%O
2
dry.
4. MakesurethattheQGO20O
2
sensorhasbeenactivatedforatleast2hoursandisupto
temperature.ThisgivestheZirconiumcelltimetoheatsoakandalsotoburnoffany
contaminants.Thetemperatureofthecellcanbecheckedifdesiredthroughthefollowing
menupath:
Params&Display>O2Module>ProcessData>QGOSensorTemp
5. Withtheburneroff(Phase12),setthefuelrichlimit(O2Alarmvalue)foreachpoint.Thiscan
bedonewiththeburneroffsincethesevalueshavealreadybeenfoundandrecordedduring
RatioControlCurvecommissioning(seeabove).OnceintotheO2Alarmcurve,simplyenterin
therecordedvalueforeachpointandsaveeachpoin
t.ToaccesstheO2Alarmcurve,usethe
followingmenupath:
Params&Display>O2Contr/Alarm>GasSettings>O2Alarm >O2Alarm
6. Withtheburneroff(Phase12),setthefuelleanlimit(O2MaxValue)basedonthevaluesthat
havealreadybeenfoundandrecordedforPoint1andPoint10duringRatioControlCurve
commissioning(seeabove).Tosetthefuelleanlimit,usethefollowingmenupath:
Params&Display>O2Contr/Alarm>GasSettings>O2Alarm >O2MaxValue
7. Thetarget%O
2
(recordedabove)willbeusedfortheO
2
ControlCurve.TheO
2
ControlCurve
pointsshouldbesettothetarget%O
2
withinabandof(+0.2/‐0.0).
8. Whenitissafetodosoandwhenthereisadequateloadavailable,starttheburner/boilerand
letitwarmuptooperatingtemperature.
9. AccesstheO
2
RatioControlCurveandtheO
2
ControlCurveusingthefollowingmenupath:
Params&Display>O2Contr/Alarm>GasSettings>O2Control
10. OncetheO
2
ControlCurveisentered,Point2shouldbedisplayed.PressingEnteragainshould
drivetheburnertoPoint2ifitisnotalreadythere.WhentheburnerisdrivingtoPoint2,a
carat(>)willbedisplayed.OncetheburnerisatPoint2,acolon(:)willbedisplayed.Iftheaux
3actuatorisusedforFGRandFGRMode
isnotsetfor“Aux3onCurve”,apound(#)indicatesthe
aux3actuatorhasnotreleasedtothecurve.
HOME