SCCInc. Page17 Section6
b. MaketheburnerdrivetoPoint2immediatelyafterlightoff.Thiscanbedonebysetting
parameterStartPointOpto2usingthefollowingmenupath:
Params&Display>RatioControl>GasSettings>StartPointOp=2
18. Iftheburnerneedsairtemperaturecompensationafterlightoff(mostultralowNOxmesh
burners),activateairtemperaturecompensation.Multiplemode
softemperature
compensationareavailable;themostoftenusedmodeis“IgnPtWithTC”.Thismodewillenable
temperaturecompensation afterlightoffandatPoint2beforetheO
2
trimengages.
Temperaturecompensatedlightoffcanbeactivatedusingthefollowingmenupath:
Params&Display>O2Contr/Alarm>GasSettings>Startmode>Startmode
NOTE:Airtemperaturecompensationrequiresanairtempera turesensorwiredtothe
LMV52.440.
SeeO
2
TrimConfiguration(Parameterization)BeforeCommissioning”abovefor
moreinformation.
19. TheO
2
trimcannowbeactivatedinoneoftwomodes.Mode“conAutoDeac”allowstheO
2
trimtoworkaslongasthemeasured%O
2
doesnotexceedtherichlimit(O
2
Alarm)orthelean
limit(O
2
MaxValue).Ifeitheroftheselimitsisexceeded,theO
2
trimwilldeactivateandthe
burnerwillrunonthenormalRatioControlCurves.Mode“O2ControlalsoallowstheO
2
trim
towork,exceptthatifthelimitsareexceededalockoutwilloccur.Mode“conAutoDeac”is
typicallyused.TosettheO
2
controloperatingmode,usethefollowingmenupath:
Params&Display>O2Contr/Alarm>GasSettings>OptgMode
20. TheO
2
trimisnowcommissionedandactivated.Someadditionaltuningmayberequired
dependingontheapplication.See"PostCommissioningTuning"laterinthissectionformore
information.