LMVSeriesTechnicalInstructions
DocumentNo.LV51000
SCCInc. Page21 Section6
O2MaxManVariableandO2MinManVariableTheseparameterssethowmuchtheO
2
systemcantrim
inanattempttoachievetheO
2
setpoint‐essentiallythetrimlimitsfortheO
2
system.
O2MaxManVariablesetshowmuchthesystemcanincreasetheairrate.Likewise,O2MinManVariable
setshowmuchthesystemcandecreasetheairrate.
Menupath:Params&Display>O2Contr/Alarm>GasSettings>ControlParam
ThesetrimlimitsmustbesetsothattheO
2
systemcanachievetheO
2
setpoint.However,thelimits
shouldnotbesetinawaythatallowstheburnertorunatanunsafefuelairratio.
Ideally,theO
2
trimsystemmustcompensatefortwomainenvironmentalconditions.Theseconditions
areambientairtemperatureandbarometricpressure.Figure68illustrateshowmuchthemanipulated
variableneedstochangetocompensatefortheseenvironmentalconditions.ThechartinFigure68
andtheexampleinFigure69serveasaguidelineforsettingtheO2MaxManVariableand
O2MinManVariableparameters.
Figure68:Theoretic
alChangeoftheManipulatedVariablewithChangesinAmbientTemperature
andPressure
WhentheO
2
ControlCurveiscommissioned,allburnerswillbeat(0,0)onthechart,wheretheXaxis
andYaxiscross.Asairtemperatureandbarometricpressurechangefromtheairtemperatureand